Cable Routing Procedures
for Dell™ PowerEdge
R510 Systems
A Dell Technical White Paper
Dell │ Datacenter Infrastructure Engineering
By Riyad Moe and Jose L. Flores
November 2009
Vedere la pagina 0
1 2 3 4 5 6 ... 10 11

Sommario

Pagina 1 - A Dell Technical White Paper

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems A Dell Technical White Paper Dell │ Datacenter Infrastructure Engineering B

Pagina 2

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 8 Section 3: Replacing a Power Supply on a PowerEdge™ R510 System With a CMA 3.1 R

Pagina 3 - Contents

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 9 Figure 10: Replacing the Power Supply Section 4: Cabling a PowerEdge™ R510 Sys

Pagina 4 - Introduction

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page ii THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND

Pagina 5

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 1 Contents Introduction ...

Pagina 6

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 2 Introduction This white paper covers recommended cable routing procedures for De

Pagina 7

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 3 1.2 Installing the Inner CMA Attachment Bracket As described in the Rack Install

Pagina 8

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 4 NOTE: For guidelines on how to route cables within the rack, refer to the Dell B

Pagina 9

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 5 Figure 5: Left-Side Mounted CMA Installation 1.6 Right-Side Mounting Instructi

Pagina 10

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 6 Figure 6: Right-Side Mounted CMA Installation

Pagina 11

Cable Routing Procedures for Dell™ PowerEdge™ R510 Systems Page 7 Figure 7: Cable Routing Without a CMA 2.2 Removing the CMA Brackets for Shallow